Wall-hung gas boilers
Model 4
24-hour national consultation hotline
400-6685315
Product details

Product details

1. EVI jet enthalpy increase technology, powerful heating.

2. Intelligent frost, more thorough defrosting and shorter time.

3. Ultra-wide chip spacing, internal thread copper tube, increase heat absorption efficiency.


Specifications
Model 4LDKFXFC -032 UIILDKFXFC -045 UIILDKFXFC -065 UIILDKFXFC -075 UIILDKFXFC -090 UIILDKFXFC -150 UIILDKFXFC -180 UII
Capability/Energy efficiencyNominal heating capacitykW / --20 / 2.5428.5 / 2.4538 / 2.450 / 2.458 / 2.35100 / 2.37118 / 2.39
A7 W45 / COPkW / --28.5 / 3.5539.5 / 3.263 / 3.575 / 3.590 / 3.5147 / 3.5175 / 3.5
A-6 W41 / COPkW / --23.5 / 2.7537.1 / 2.855 / 2.864 / 2.866 / 2.8110 / 2.8132 / 2.8
A-20 W41 / COPkW / --15.5 / 2.123.1 / 2.130.4 / 2.142.2 / 2.150.6 / 2.183.1 / 2.198.5 / 2.1
Nominal cooling capacitykW / --24.5 / 2.8135.5 / 2.7550 / 3.060 / 3.165 / 2.7120 / 2.72130 / 2.71
IPLV(C) / IPLV(H)
3.6 / 2.93.6 / 2.93.6 / 2.93.6 / 2.93.6 / 2.93.6 / 2.93.6 / 2.9
Power specifications /380 V 3 N~ 50 Hz
Nominal cooling input power/currentkW/A8.7/ 16.512.9 / 33.916.7 / 43.919.4 / 51.124.1 / 63.444.1 / 11648 / 126
Nominal heating input power/currentkW/A7.86 / 14.511.6 / 30.515.8 / 41.620.8 / 54.724.7 / 6542.2 / 11149.4 / 130
Refrigerant type/charge amount-- / kgR22 / 4.5*2R22 / 5.5*2R410 A/ 10*2R410 A / 12.5*2R410 A / 12.5*2R410 A / 16*2R410 A /16*2
Heat exchanger Water sideForm/High efficiency shell and tube heat exchangerShell and tube heat exchanger
Maximum outlet water temperature60
Rated water flowm³ / h4.46.21213142530
Dimensionsmm1460 *840 *12501460 *840 *12502100 *1100 *20002100 *1100 *20002100 *1100 *20002300 *1250 *24002300 *1250 *2400
NoisedB(A)≤63≤65≤68≤68≤70≤70≤72
Net weightkg350380850950100012001300











Remarks: 1. A7W45 indicates that the test conditions are: the ambient dry/wet bulb temperature is 7°C/6°C, and the use side inlet/outlet water temperature is 40°C/45°C.
2. Nominal heating conditions: ambient dry bulb temperature -12°C, wet bulb temperature -14°C, and outlet water temperature on the use side of 41°C.
3. Nominal cooling conditions: ambient dry bulb temperature is 35°C, and outlet water temperature on the use side is 7°C.
4. Models and parameters will be changed due to product improvement without prior notice. The specific parameters are subject to the nameplate parameters.